Daikin FLY35GV1NB [43/67] No going off

Daikin FLY35GV1NB [43/67] No going off
SiE-84
Service Manual 35
YES
NO
Printed circuit board diagnostic flow chart (Checking order : outdoor - indoor)
Disconnect the power supply
and then connect it again.
Recovered to normal.
External factors
(noise, etc.) other
than failure may be
considered.
The outdoor printed
circuit board is faulty.
Disconnect the
power supply,
remove the 2nd wire
and then connect the
power supply again.
The indoor printed
circuit board is faulty.
Replace the indoor
printed circuit board
and
The outdoor printed circuit
board is faulty or the power
supply system is abnormal.
If the indoor printed circuit is
faulty, replace the indoor
printed circuit board and
Diagnose
outdoor
products.
The indoor micro-computer
is normal.
Check LED A.
Remove the 2nd wire of the
indoor and outdoor control
wires.
START
LED A = Blinking
Lighting up or
going off.
LED A = Blinking
LED A = Lighting up
Red LED = Going off
LED A = Blinking
To indoor
YES
YES
YES
NO (going off).
NO
NO
(to the next page)
Lighting
up
YES
NO
Outdoor
abnormality is
detected.
Check LED.
SIE2-84.book Page 35 Wednesday, May 30, 2001 10:29 AM