SiBE18-821 Test Operation
Test Operation 119
1.1.6 When the No. of Indoor Unit Has Been Changed, or Indoor (BP) or
Outdoor Unit PC Board Has Been Changed, or the System is
transferred
Be sure to push and hold the RESET button for 5 seconds. If not, the addition cannot be
recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the
address (indoor-outdoor address, etc.)
Status
1.1.7 Air Tight test and Vacuum Drying
Air tight test: Make sure to use nitrogen gas.
Pressurize the liquid and gas pipes to 4.0 MPa (40 bar) (do not pressurize more than 4.0
MPa (40 bar)). If the pressure does not drop within 24 hours, the system passes the test. If
the pressure drops, check where the nitrogen leaks from.
Vacuum drying: Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr, –755 mm
Hg)
1. Evacuate the system from the liquid and gas pipes by using a vacuum pump for more than 2
hours and bring the system to –100.7 kPa. After keeping the system under that condition for
more than 1 hour, check if the vacuum gauge rises or not. If it rises, the system may either
contain moisture inside or have leaks.
2. Following should be executed if there is a possibility of moisture remaining inside the pipe (if
piping work is carried out during the raining season or over a long period of time, rainwater
may enter the pipe during work).
After evacuating the system for 2 hours, pressurize the system to 0.05 MPa (vacuum break)
with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to –100.7
kPa (vacuum drying). If the system cannot be evacuated to –100.7 kPa within 2 hours, repeat
the operation of vacuum break and vacuum drying.
Then, after leaving the system in vacuum for 1 hour, confirm that the vacuum gauge does not
rise.
Outdoor unit Test lamp H2P .... ON
Can also be set during operation described above.
Indoor unit If ON button is pushed during operation described above, the “UH” or “U4”
malfunction indicator blinks. (Returns to normal when automatic setting is
complete.)