Daikin RMXS112E8V1B [296/393] Troubleshooting

Daikin RMXS160E8V1B [296/393] Troubleshooting
SiBE18-821 Troubleshooting for SkyAir Indoor Unit
Troubleshooting 283
Troubleshooting
Is the limit
switch's transfer
connector correctly
connected?
Does the swing
flap motor swing?
Are the
connectors correctly
connected to X29A and
X14A on the PC
board?
Does
continuity/no continuity
reverse?
220-240 VAC?
Turn the power supply off
once and back on, and check
whether the swing flap motor
swings when the power
supply is turned back on.
Turn the power supply off
once and back on, and
measure the output voltage of
connector X29A when the
power supply is turned back
on.
Disconnect X14A, turn the
power supply off once and
back on, and check if the limit
switch has continuity when
the power supply is turned
back on.
Connect correctly.
Connect correctly.
Replace the indoor unit PCB.
Replace the swing flap
motor.
NO
YES
YES
NO
YES
YES
NO
NO
YES
NO
(Q0536)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.