Daikin RMXS112E8V1B [356/393] Troubleshooting

Daikin CTXG50EV1BS [356/393] Troubleshooting
SiBE18-821 Troubleshooting for Outdoor Unit
Troubleshooting 343
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Has
an indoor unit
once connected been
remove or its address
changed?
Is
the master
controller's connector for
setting master controller
disconnected?
Is the power
supply turned on for
indoor units displaying
malfunction?
Is
transmission wiring
disconnected or wired
incorrectly?
Is
transmission with
all indoor units
malfunctioning?
Is the
group No. of
malfunctioning indoor
units set?
Is the
transmission
wiring with the master
controller disconnected or
wired incorrectly?
Connect the connector
correctly.
NO
Reset power supply
simultaneously for all
optional controllers for
centralized control.
YES
NO
Turn indoor unit's power
supply.
NO
YES
Fix the wiring correctly.
NO
YES
NO
YES
Fix the wiring correctly.
NO
YES
Replace the central PC
board.
YES
(Q0584)
Set the group No.
correctly.
NO
Replace indoor unit PC
board.
YES