Daikin RMXS112E8V1B [358/393] Defect of outdoor unit pcb a1p

Daikin RMXS140E8V1B [358/393] Defect of outdoor unit pcb a1p
SiBE18-821 Troubleshooting for Outdoor Unit
Troubleshooting 345
7.37 Malfunction of System, Refrigerant System Address
Undefined
Remote
Controller
Display
UH
Applicable
Models
All indoor unit models
All outdoor unit models
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Improper connection of transmission wiring between outdoor unit and outdoor unit outside
control adaptor
Defect of indoor unit PCB
Defect of outdoor unit PCB (A1P)
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is
electricity
being introduce
for the first time after
installationor after an indoor
or outdoor unit PC
board has been
replaced?
Does a
malfunction
occur even after 12
minutes elapses from the
time when electricity is
introduced to indoor
and outdoor
units?
Is indoor
- outdoor and
outdoor - outdoor unit
transmission wiring
normal?
Does a
"UH" malfunction
occur for all indoor units
in the system?
Does a
malfunction occur?
After fixing incorrect wiring,
push and hold the RESET
button on the outdoor unit PC
board for 5 seconds
Normal
YES NO
YES
NO
YES
Normal
NO
Replace indoor unit PC
board.
NO
After fixing incorrect
wiring, push and hold the
RESET button on the
master outdoor unit PC
board for 5 seconds.
The unit will not run for
up to 12 minutes.
NO
YES
Replace outdoor unit PC
board (A1P).
YES
(Q0586)