Daikin RMXS112E8V1B Сервис мануал онлайн [152/393] 604226

Daikin RMXS112E8V1B Сервис мануал онлайн [152/393] 604226
SiBE18-821 Field Setting
Test Operation 139
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory set
1
Cool / Heat
Unified address
8777778
Address 0
8777777
Binary number 1
8777778
(6 digits) ~
31
8788888
2
Low noise/demand
address
8777787
Address 0
8777777
Binary number 1
8777778
(6 digits) ~
31
8788888
3 Test operation
8777788
Test operation : OFF
8777778
Test operation : ON
8777787
5 Indoor forced fan H
8777878
Normal operation
8777778
Indoor forced fan H
8777787
6
Indoor forced
operation
8777887
Normal operation
8777778
Indoor forced operation
8777787
8 Te setting
8778777
High
8777877
Normal (factory setting)
8777787
Low
8777778
9 Tc setting
8778778
High
8777877
Normal (factory setting)
8777787
Low
8777778
10
Defrost changeover
setting
8778787
Quick defrost
8777877
Normal (factory setting)
8777787
Slow defrost
8777778
12
External low noise/
demand setting
8778877
External low noise/demand:
NO
8777778
External low noise/demand:
YES
8777787
13 Airnet address
8778878
Address 0
8777777
Binary number 1
8777778
(6 digits) ~
63
8888888
16
Setting of hot water
heater
8787777
OFF
8777778
ON
8777787
20
Additional refrigerant
charging operation
setting
8787877
Refrigerant charging: OFF
8777778
Refrigerant charging: ON
8777787
21
Refrigerant recovery /
vacuuming mode
setting
8787878
Refrigerant recovery /
vacuuming: OFF
8777778
Refrigerant recovery /
vacuuming: ON
8777787
22
Night-time low noise
setting
8787887
OFF
8777777
Level 1 (outdoor fan with 8 step or lower)
8777778
Level 2 (outdoor fan with 7 step or lower)
8777787
Level 3 (outdoor fan with 6 step or lower)
8777788

Содержание