8 x Errors, malfunctions and messages
8.3 Fault codes
In the case of all malfunctions / error messages due to possibly defective sensors, all associated connection cables, con-
nection points (plug contacts correctly in place) and printed circuit boards must be checked before replacing the sensor.
Component allocation: see fig. 3-1 to fig. 3-5 and fig. 8-4
Device-internal circula-
tion pump is excessively
noisy while running
Air in the water circuit
Fully vent the heating system and device-internal
circulation pump.
Noises caused by vibrations.
Check the Daikin Altherma EHS(X/H), its components
and covers to ensure they are fastened correctly.
Bearing damage in the device-internal circula-
tion pump.
Reduce pump speed [Min Perform Pump] and [Max
Perform Pump]).
Replace device-internal circulation pump.
Water pressure at pump inlet too low.
On the controller (rotary switch setting "Info"
)
check whether there is adequate water pressure
(>0.5 bar).
Check that the pressure gauge is working correctly
(connect an external pressure gauge).
Check the primary pressure in the expansion
container and the water pressure, if necessary, refill
the heating water and reset the primary pressure
(see chapter 7.4).
Safety pressure relief
valve is leaking or always
open.
Expansion tank is defective.
Replace expansion tank.
Water pressure in the heating system is too
high.
On the control unit (rotary switch position "Info"
)
check that the water pressure lies beneath the stated
maximum pressure. If necessary, bleed the water until
the pressure lies in central permissible range.
Safety pressure relief valve is stuck.
Check safety pressure relief valve and if necessary,
replace it.
Turn the red knob on the safety pressure relief
valve counterclockwise. If you can hear a rattling
noise, the safety pressure relief valve needs
replacing.
Tab. 8-1 Possible malfunctions of the Daikin Altherma EHS(X/H)
Code Malfunction /
Error messages
Component/Designation Causes and possible error correction
Display Internal
E9001 80 Fault T-return
Return flow temperature
sensor t
R2
Sensor or connection cable defective.
Check, replace.
E9002 81 Fault feed flow
Flow temperature
sensor t
V1
or t
V, BH
Sensor or connection cable defective.
Check, replace.
E9003 89
Frost protection
function error
Plate heat exchanger
(PHE)
Measured value t
V1
<0 °C
Failure of the frost protection function for the plate heat
exchanger because the water flow is too low. See error code
E9004 / 7H.
Failure of the frost protection function of the plate heat
exchanger because there is a lack of coolant in the system.
See error code E9015 / E4.