Daikin RZQ140B7W1B [154/326] Equipment does not operate

Daikin RZQ100B7W1B [154/326] Equipment does not operate
Troubleshooting ESIE05-03
3–6 Part 3 Troubleshooting
3
1
3
4
5
1.3.1 Equipment does not operate
Applicable Model All models of SkyAir series
Error Detection
Method
Error Generating
Condition
Possible Causes
P Fuse blown or disorder of contact in operation circuit
P Faulty operation switch or contact point
P Faulty high pressure switch
P Faulty magnetic switch for fan motor
P Activation or fault of overcurrent relay for fan motor
P Faulty overcurrent relay for compressor
P Faulty compressor protection thermostat
P Insufficient insulation in electric system
P Faulty contact point of magnetic switch for compressor
P Malfunction of compressor
P Fefective remote controller or low batteries (wireless)
P Check if address is set correctly on wireless R.C.
ESIE05-03.book Page 6 Wednesday, April 6, 2005 4:09 PM