Daikin RZQ140B7W1B [228/326] Dc output overcurrent instantaneous l5

Daikin RZQ100B8V3B [228/326] Dc output overcurrent instantaneous l5
Error Codes: Outdoor Units ESIE05-03
3–80 Part 3 Troubleshooting
3
1
3
4
5
3.15 DC Output Overcurrent (Instantaneous) (L5)
Remote Controller
Display
L5
Method of
Malfunction
Detection
Malfunction is detected by converting the current flowing to power transistor into voltage with CT1 (DC
current sensor).
Malfunction
Decision
Conditions
When overcurrent has run to power transistor.
(Actuated even by instantaneous overcurrent)
Supposed Causes
P Faulty compressor coil (disconnection, poor insulation)
P Compressor startup malfunction (mechanical lock)
P Faulty inverter PC board
P Instantaneous fluctuation of power supply voltage
P Faulty compressor (if bearing is scratched)
P The stop valve is left in closed.
ESIE05-03.book Page 80 Wednesday, April 6, 2005 4:09 PM