Daikin RZQ140B7W1B [173/326] Procedure of self diagnosis by remote controller

Daikin RZQ125B8V3B [173/326] Procedure of self diagnosis by remote controller
ESIE05-03 Troubleshooting
Part 3 Troubleshooting 3–25
33
4
5
1
1.4 Procedure of Self-Diagnosis by Remote Controller
The inspection/test
button
The following modes can be selected by using the [Inspection/Test Operation] button on the
remote control.
Indoor unit settings can be made.
P Filter sign time
P Air flow direction
P Others
Service data can be obtained.
P Malfunciton code history
P Temperature data of various section
s
Service settings can be made.
P Forced fan ON
P Air flow direction/volume setting
Depress Inspection/Test Operation
button for more than 4 seconds.
Following codes can be checked.
P Malfunction codes
P Indoor model code
P Outdoor model code
Press Inspection/Test Operation button once.
Press Inspection/Test Operation button once.
Press Inspection/Test Operation button once.
Or after 30 minutes.
Depress Inspection/Test Operation
button for more than 4 seconds.
Press Inspection/Test Operation
button once.
After 10 seconds
Thermostat is forcibly turned on.
Local
setting
mode
Service
mode
Normal
mode
Inspection
mode
Test
operation
mode
ESIE05-03.book Page 25 Wednesday, April 6, 2005 4:09 PM