Daikin RZQ140B7W1B [201/326] Thermistor abnormality c4 c5 c9

Daikin RZQ71B8V3B [201/326] Thermistor abnormality c4 c5 c9
ESIE05-03 Error Codes: Indoor Units
Part 3 Troubleshooting 3–53
4
5
1
3
2.8 Thermistor Abnormality (C4, C5, C9)
Error code The table below describes the two thermistor abnormalities.
LED indications The table below shows the LED indications.
Error generation The error is generated when during compressor operation:
P Thermistor input > 4.96 V, or
P Thermistor output < 0.04 V.
Causes The possible causes are:
P Malfunctioning connector connection
P Malfunctioning thermistor
P Malfunctioning PCB
P Broken or disconnected wire.
Checking
thermistors
See page 3–106.
Error Description
C4
Malfunctioning heat exchanger thermistor system.
C5
Malfuncioning gaspipe thermistor system.
C9
Malfunctioning suction air thermistor system.
Operation HAP (green) HBP (green)
Normal
cc
Malfunctioning
cc
ESIE05-03.book Page 53 Wednesday, April 6, 2005 4:09 PM