Daikin RZQ140B7W1B [172/326] 24 part 3 troubleshooting

Daikin RZQ125B8V3B [172/326] 24 part 3 troubleshooting
Troubleshooting ESIE05-03
3–24 Part 3 Troubleshooting
3
1
3
4
5
Troubleshooting
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Is the
limit switch’s
transfer connector
correctly
connected?
Does the flap swing?
Are the
connectors correctly
connected to X29A and
X14A on the
PC board?
Is continuity/no
continuity reversed?
220 - 240 VAC?
Turn the power supply off once
and back on, and measure the
output voltage of connector
X29A when the power supply is
turned back on.
Disconnect X14A, turn the
power supply off once and back
on, and check if the limit switch
has continuity when the power
supply it turned back on.
Turn the power supply off once
and back on, and check whether
the swing flap motor swings
when the power supply is turned
back on.
YES
NO
NO
YES
YES
YES
NO
NO
YES
NO
Connect correctly.
Connect correctly.
Replace the indoor unit
PC board.
Replace the swing
motor assembly.
ESIE05-03.book Page 24 Wednesday, April 6, 2005 4:09 PM