Daikin RZQ140B7W1B Сервис мануал онлайн [18/326] 607213

Daikin RZQ140B7W1B Сервис мануал онлайн [18/326] 607213
Introduction ESIE05-03
viii
3
1
4
5
Copper tube
material and
thickness
* O: Soft (Annealed)
H: Hard (Drawn)
Flaring tool
P Specifications
Dimension A
Pipe size
R407C R410A
Material
Thickness
tmmj
Material
Thickness
tmmj
φ6.4 O 0.8 O 0.8
φ9.5 O 0.8 O 0.8
φ12.7 O 0.8 O 0.8
φ15.9 O 1.0 O 1.0
φ19.1 O 1.0 1/2H 1.0
Nominal size Tube O.D.
A
Do
Class-2 (R410A) Class-1 (Conventional)
1/4 6.35
9.1 9.0
3/8 9.52
13.2 13.0
1/2 12.70
16.6 16.2
5/8 15.88
19.7 19.4
3/4 19.05
24.0 23.3
Flare gauge
+0
-0.4
ESIE05-03.book Page viii Wednesday, April 6, 2005 4:09 PM