Airwell SLS 2702 [25/77] Operation

Airwell SLS 3002 [25/77] Operation
Page 24
Operation
Code Alarm Description Comp 1 Comp 2 Fan #1 Fan #2 Pump Notes
Status Status Status Status Status
AL00
Compressor stop
Due to auto-reset alarm. Just stored into the historical
AL01
Wrong power
Off Off Off Off Off
Phase monitor (1)
AL02
Antifreeze alarm
Off Off Off Off On
AL03
Interlock
Off Off Off Off Off
AL04
Flow switch alarm
Off Off Off Off Off
AL05
System #1 low suction pressure
Off On Off On On
AL06
System #2 low suction pressure
On Off On Off On
AL07
System #1 high discharge pressure
Off On Off On On
AL08
System #2 high discharge pressure
On Off On Off On
AL09
Compressor #1 thermal protection
Off On Off On On
AL10
Compressor #2 thermal protection
On Off On Off On
AL11
Recovery antifreeze alarm
On On On On On
AL12
System #1 group #1 fan thermal protection
On On Off gr. # 1 On On
AL13
System #1 group #2 fan thermal protection
On On Off gr. # 2 On On
AL14
System #2 group #1 fan thermal protection
On On On Off gr. # 1 On
AL15
System #2 group #2 fan thermal protection
On On On Off gr. # 2 On
AL16
System #1 compressor differential pressure
Off On Off On On
AL17
System #2 compressor differential pressure
On Off On Off On
AL18
Clock board failure
On On On On On
AL21
B1-Tin sensor failure
Off Off Off Off On
AL22
B2-LP1 sensor failure
Off On Off On On
AL23
B3-DP1 sensor failure
Off On On On On
AL24
B4-Tair sensor failure
On On On On On
AL25
B5-Tout sensor failure
Off Off Off Off On
AL26
B6-LP2 sensor failure
On Off On Off On
AL27
B7-DP2 sensor failure
On Off On On On
AL28
B8-Tplan sensor failure
Off Off Off Off On
AL29 B9-Trin/TC1
sensor failure
On On On On On note (2)
AL30 B10-Trout/TC2
sensor failure
On On On On On note (2)
AL31 System #1 compressor maintenance On On On On On
AL32 System #2 compressor maintenance On On On On On
AL33 Pump maintenance On On On On On
AL36 System #1 Low pressure Off On Off On On
Just stored into the historical
AL37 System #2 Low pressure On Off On Off On
Just stored into the historical
Note:
1 = Check power phases rotation and/or minimum voltage. It works only in case the Phases Monitor (accessory) is installed.
2 = It forces to leave the recovery mode. Recovery mode inhibited.
6.3 Functions / Keys / Configurations
I
Alarms table
I
“Menu” key
Pushing the “Menu” key the main mask is displayed:
U:1 RWT ................... 0.0 °C
SYS#1: OFF
SYS#2: OFF
Unit.. ON
In this mask the following items are displayed:
– unit serial number and control temperature
– system #1 status
– system #2 status
– unit status