The Digital Controller ESIE07-04
2–48 Part 2 – Functional Description
3
1
2
4
5
Compressor
load/unload pulses
This screen allows you to set the compressor load and unload pulses.
Unloading
parameters
This screen allows you to set the unloading parameters.
Warning : Verify during commissioning.
Loading
parameters
This screen allows you to set the loading parameters.
Warning : Verify during commissioning.
Number of Pulses to Load Comp. 015
Number of Pulses to Unload Comp. 015
P Pulse Time : Time of the unload pulses
P Min Pulse Period : Minimum time between two unload pulses
P Max Pulse Period : Maximum time between two unload pulses
Unloading
Pulse Time 00.3 s
Min Pulse Period 01 s
Max Pulse Period 090 s
P Pulse Time : Time of the load pulses
P Min Pulse Period : Minimum time between two load pulses
P Max Pulse Period : Maximum time between two load pulses
Loading
Pulse Time 00.3 s
Min Pulse Period 05 s
Max Pulse Period 090 s