Daikin EWADC14BJYNN [336/346] Seasonal shut down

Daikin EWADC14BJYNN [336/346] Seasonal shut down
Maintenance ESIE07-04
5–10 Part 5 – Maintenance
3
1
55
1.5 Seasonal Shut-down
Procedure P Turn the Q1 selector to Off position. The compressor will carry out its pump-down cycle and then
stop.
P Repeat the sequence for all the selectors Q2, (Q3 and Q4) to stop all the other compressors.
P Switch the “Q0” selector from “Local” to off position.
P Push the “On/Off” button on the keypad to de-energise the unit, green light become off.
P Open the circuit breaker Q12 to stop the auxiliary circuit.
P Open the main switch Q10 to remove the power supplier to the unit. In this condition the oil electric
heater is off. When you restart the unit before switching on the compressors wait at least 12 hours
to heat the oil.
P Close the shut-off valves of the refrigerant circuits.
P Switch off the water pumps
P Empty the water heat exchangers or fill them with glycol for freeze protection.

Содержание

Скачать