Functional Control ESIE07-04
2–112 Part 2 – Functional Description
3
1
2
4
5
Manufacturer menu
These parameters are used for the PID function
Maintenance menu
The controller will calculate the fan speed according to the HP to match the entered HP setpoint.
Cond Regulation
Regul. Band
Neutral Band
05.0 bar
00.0 bar
Cond. Regulation
Integral Time 600 s
Derivative Time 001 s
Condensation
Setpoint 09.0 bar
regulation
band
Setpoint 9.0
HP (bar)
11.5
6.5