ELECTRICAL SPECIFICATION
MODEL
EWYT430B-
SRA2
EWYT490B-
SRA2
EWYT540B-
SRA2
EWYT590B-
SRA2
EWYT630B-
SRA2
POWER SUPPLY
Phases
3
3
3
3
3
Frequency
50
50
50
50
50
Voltage
400
400
400
400
400
Voltage tolerance
Minimum
-10%
-10%
-10%
-10%
-10%
Voltage tolerance
Maximum
10%
10%
10%
10%
10%
UNIT
Maximum inrush
current
666
712
757
795
825
Nominal running
current cooling
251
292
330
353
373
Maximum running
current
334
379
425
463
493
Maximum current
for wires sizing
367
417
468
509
542
FANS
Nominal running
current cooling
18
18
18
23
23
COMPRESSORS
Phases
3
3
3
3
3
Voltage
400
400
400
400
400
Voltage tolerance
Minimum
-10%
-10%
-10%
-10%
-10%
Voltage tolerance
Maximum
10%
10%
10%
10%
10%
Maximum running
current
301
372
443
447
452
Starting method
DOL
DOL
DOL
DOL
DOL
EWYT~B-XS
MODEL
EWYT085B-
XSA1
EWYT115B-
XSA1
EWYT135B-
XSA1
EWYT175B-
XSA1
EWYT215B-
XSA1
EWYT215B-
XSA2
POWER SUPPLY
Phases
No.
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
213
329
343
465
497
412
Nominal running current cooling
A
53
65
75
99
123
122
Maximum running current
A
70
87
101
133
165
170
Maximum current for wires sizing
A
77
96
111
146
182
187
FANS
Nominal running current cooling
A
6
8
8
9
11
13
COMPRESSORS
Phases
No.
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
10%
Maximum running current
A
64
92
89
146
151
184
Starting method
DOL
DOL
DOL
DOL
DOL
DOL