Function 121
6.6 Electronic Expansion Valve Control
• Electronic expansion Valve Control
In cooling, to maximize the capacity of indoor unit heat exchanger (evaporator), operate the
electronic expansion valve under PI control so that the evaporator outlet superheated degree
(SH) will become constant.
Furthermore, the default value of the optimal evaporator outlet superheated degree (condenser
outlet subcooled degree) is 5 deg. However, this default value varies with the operating
performance.
Cooling SH=TH
2
-TH
1
SH
: Evaporator outlet superheated degree
TH
1
: Temperature (°C) detected with the liquid thermistor
TH
2
: Temperature (°C) detected with the gas thermistor