Daikin FXDQ32PVET [246/394] Outdoor unit current sensor malfunction

Daikin FXDQ32PVE [246/394] Outdoor unit current sensor malfunction
Si34-704 Troubleshooting by Indication on the Remote Controller
Troubleshooting 235
3.25
J2
Outdoor Unit: Current Sensor Malfunction
Remote
Controller
Display
J2
Applicable
Models
RXQ5P~54P
Method of
Malfunction
Detection
Malfunction is detected according to the current value detected by current sensor.
Malfunction
Decision
Conditions
When the current value detected by current sensor becomes 5A or lower, or 40A or more during
standard compressor operation.
Supposed
Causes
Faulty current sensor (A6P, A7P)
Faulty outdoor unit PC board
Defective compressor
Troubleshooting
(V3071)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
current sensor
mounted on the T-phase
(A6P) and R-phase
(A7P) wire?
Are the
current sensors inversely
connected to two STD
compressors?
Is the
connector for
current sensor
connected to X25A, X26A
on outdoor unit
PC board
(A1P)?
Replace current sensor or outdoor
unit PC board.
Connect the connector, and
operate unit again.
NO
NO
Mount the current sensor
correctly, and operate unit again.
YES
Correct the connections between
the current sensors and the STD
compressors.
Applicable
compressor coil wire is
broken.
YES
Replace compressor.
NO
NO
YES
YES
Check the current sensor corresponding to the malfunction
code “J2” in the monitor mode.
(Refer to P. 194 ~ 195 for how to check)
Check 4 shows as follows:
Current sensor for constant rate compressor 1
Check 4 shows as follows:
Current sensor for constant rate compressor 2
Explanation for “ ”
Master unit
Slave unit 1
Slave unit 2
System