Si34-704 Troubleshooting by Indication on the Remote Controller
Troubleshooting 213
3.11
C9
Indoor Unit: Malfunction of Thermistor (R1T) for
Suction Air
Remote
Controller
Display
C9
Applicable
Models
AII indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by suction air temperature
thermistor.
Malfunction
Decision
Conditions
When the suction air temperature thermistor becomes disconnected or shorted while the unit is
running.
Supposed
Causes
Defect of indoor unit thermistor (R1T) for air inlet
Defect of indoor unit PC board
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table on P361.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Remove the thermistor from
the indoor unit PC board, and
then insert it again.
Remove the thermistor from
the indoor unit PC board, and
then make resistance
measurement of the thermistor
using a multiple meter.
Normal (The malfunction is
caused by faulty contact.)
YES
NO
Replace the indoor unit PC board.
YES
Is the
thermistor normal?
Replace the thermistor (R1T).
NO
5 k to 90 k