Daikin FXDQ32PVET [170/394] Caution

Daikin RXQ42PHY1 [170/394] Caution
Si34-704 Field Setting
Test Operation 159
Setting by dip switches
Using dip switches on the PC board enables field setting shown below. However, make no
changes of factory settings except for DS1-1.
Refer “DS1-1~4, DS2-1~4 setting detail” on next page.
Dipswitch
Setting item Description
No. Setting
DS1-1
ON
Cool / Heat select
Used to set cool / heat select by Cool/Heat selector
equipped with outdoor unit.
OFF (Factory set)
DS1-2
~DS1-4
ON
Not used Do not change the factory settings.
OFF (Factory set)
DS2-1
~4
ON
Not used Do not change the factory settings.
OFF (Factory set)
Caution
Setting at replacement by spare PC board
DIP switch Setting after changing the main P.C.Board(A1P) to spare parts P.C.B.
After the replacement by the spare PC board, be sure to make settings shown below.
When you change the main P.C.Board(A1P) to spare parts P.C.B., please carry out the following
setting.
DIP Switch Detail
If the DS1-1~1-4, DS2-2~2-4 setting has not been carried out, error code “UA” are displayed
and unit can not be operated.
DS No. Item Contents
DS1-1 Cool/Heat change
over setting
ON
Do not Set.
OFF
(Factory
setting of spare
PC board)
Set for cooling only
DS1-2 Power supply
specification
ON 200V class (220V)
OFF
(Factory
setting of spare
PC board)
400V class (380V)
DS1-3 Cooling only/Heat-
pump setting
ON Cooling only setting
OFF
(Factory
setting of spare
PC board)
Do not set.
DS1-4 Unit allocation
setting
ON
Make the following settings according to allocation of
unit. (All models are set to OFF at factory.)
DS2-1
OFF (Factory
setting of spare
PC board)
DS2-2 Model setting
DS2-3
DS2-4
1 2 3 4 1 2 3 4
DS1 DS2
ON
OFF
ON
OFF
Initial conditions of dip switches
Make the following settings according to models of outdoor units.
(All models are set to OFF at factory.)
RXQ5P RXQ8P RXQ10P RXQ12P RXQ14P RXQ16P RXQ18P
DS2-2 OFF OFF ON OFF ON OFF ON
DS2-3 OFF ON ON OFF OFF ON ON
DS2-4 OFF OFF OFF ON ON ON ON
Domestic
Japan
Overseas
General
Europe
DS1-4
OFF OFF ON
DS2-1
OFF ON OFF