Daikin FXDQ32PVET [290/394] Troubleshooting

Daikin FXDQ20PVET [290/394] Troubleshooting
Si34-704 Troubleshooting by Indication on the Remote Controller
Troubleshooting 279
Troubleshooting
YES
NO
YES
NO
Correct the connecting wires of
the outdoor multi and then reset
the power supply.
Replace the main PCB of the
outdoor unit.
Remove the connecting wires of
the outdoor multi and then reset
the power supply.
YES
NO
Check 3
Check 3 Check 4
Check 4
Diagnosis Flow 3
Diagnosis Flow 4
Diagnosis Flow 5
Check
the connection status
of connecting wires of Multi Slave 2
with outdoor multi. Check if the wiring
is not disconnected or is about
to be disconnected.
Check
if the outdoor unit is
RXQ5P.
Check 3
Check
the connection status
of connecting wires of Multi Slave 1
with outdoor multi. Check if the wiring
is not disconnected or is about to
be disconnected.
Replace the outdoor unit main
PCB of the Multi Slave 1.
Correct the connecting wires of the
outdoor multi and then reset the
power supply.
Replace the outdoor unit main
PCB of the Multi Slave 2.
Check 4
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.

Содержание