Daikin FXDQ32PVET [283/394] Troubleshooting

Daikin FXDQ20PVET [283/394] Troubleshooting
Troubleshooting by Indication on the Remote Controller Si34-704
272 Troubleshooting
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
NO
NO
YES
NO
YES
YES
YES
YES
YES
NO
NO
NO
NO
YES
NO
NO
NO
YES
YES
NO
YES
(
Go on to the next page.
LED lamp display
)
Check the detailed malfunction
status in the monitor mode.
(Refer to P. 196~197 for how
to check.)
Reset the power supply here.
In Check 4,
LED lamp indicates
as follows:
Check if
indoor unit PCB or outdoor
unit PCB has been replaced. Or check
if indoor/ outdoor, outdoor/ outdoor
connecting wires
are normal.
Check if all
the indoor remote controllers
within the same refrigerant
circuit display
“U4”.
Check if the
indoor/ outdoor, outdoor/
outdoor connecting wires
are normal.
Check if the
voltage between L1, L2
terminals on the outdoor unit
PCB is 380~415V.
The fuse on
the outdoor unit PCB
is blown.
Check if
the normal condition
monitor for the microcomputer
(HAP) on the outdoor unit
PCB blinks.
Check if
the LED in preparation
mode (H2P) on the outdoor
unit PCB blink.
Lights do not
go out for 12 minutes
or more.
Check if
the indoor/ outdoor,
outdoor/ outdoor connecting
wires are normal.
Check if
the operation is normal
with 1 circuit after outdoor/ outdoor
connecting wires are
removed.
Press the rewiring button on the
main PCB of the master outdoor
unit. Keep pressing for 5 seconds
or more. (Operation does not start
for a maximum 12 minutes.)
Replace indoor unit PCB.
Correct the connecting wires.
Correct the voltage (380~415V).
Replace the fuse.
Replace the outdoor unit PCB.
Press the rewiring button on the
main PCB of the outdoor unit.
Keep pressing for 5 seconds or
more.
Correct the connecting wires.
Replace the main PCB of outdoor
unit.
Fix DIII Net extension adapter.