Daikin FXDQ32PVET [225/394] Indoor unit malfunction of thermistor r4t for discharge air

Daikin FXDQ20PVET [225/394] Indoor unit malfunction of thermistor r4t for discharge air
Troubleshooting by Indication on the Remote Controller Si34-704
214 Troubleshooting
3.12
CA
Indoor unit: Malfunction of Thermistor (R4T) for
discharge Air
Remote
Controller
Display
CA
Applicable
Models
FXMQ-MF
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by discharge air thermistor.
Malfunction
Decision
Conditions
When the discharge air thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Defect of indoor unit thermistor (R4T) for discharge air
Defect of indoor unit PC board
Troubleshooting
Check if
the unit starts normal
operation.
(1)
YES
Normal (defective connection of
the connector).
Remove thermister from indoor
unit PCB and then insert it
correctly.
Remove thermister from indoor
unit PCB and measure the
resistance value by using
tester.
YES
Check if
it is normal, 5- 90
(2)
NO
Replace thermister.
Replace indoor unit PC board.
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.