Daikin FXDQ32PVET [258/394] Outdoor unit defective inverter pcb

Daikin FXDQ25PVET [258/394] Outdoor unit defective inverter pcb
Si34-704 Troubleshooting by Indication on the Remote Controller
Troubleshooting 247
3.33
L1
Outdoor Unit: Defective Inverter PCB
Remote
Controller
Display
L1
Applicable
Models
RXQ5P~54P
Method of
Malfunction
Detection
Malfunction is detected based on the current value during waveform output before starting
compressor.
Malfunction is detected based on the value from current sensor during synchronous operation
when starting the unit.
Malfunction
Decision
Conditions
Overcurrent (OCP) flows during waveform output.
Malfunction of current sensor during synchronous operation.
IPM failure.
Supposed
Causes
Inverter PCB (A3P)
z
IPM failure
z
Current sensor failure
z
Drive circuit failure
Troubleshooting
Check if
the unit recovers to
normal operation.
Check 4
Check if the power
transistor is
normal.
YES
Check if
insulation resistance of
the compressor is 100k
and above.
NO
YES
Check 4
Check if the power
transistor of the fan
driver is normal.
NO
NO
YES
Power off the unit then
supply power again.
YES
NO
There are some other possible
external factors except failure.
(External noise, thunder, etc.)
Replace the compressor and
compressor inverter PCB (A3P) at
the same time.
Replace the inverter PCB (A3P).
Replace the compressor inverter
PCB (A3P) and fan inverter PCB
(A4P, A8P).
Replace the inverter PCB (A3P).
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check 4
: Referring to the information on page 306.