Daikin FXDQ32PVET [262/394] Troubleshooting compressor inspection

Daikin FXDQ20PVET [262/394] Troubleshooting compressor inspection
Si34-704 Troubleshooting by Indication on the Remote Controller
Troubleshooting 251
Troubleshooting Compressor inspection
Correct the wiring and
connection.
Replace inverter
compressor.
Replace inverter
compressor.
Replace inverter PCB
(A3P).
Continue operation.
Momentary power failure
is possible.
Replace compressor lead
wires.
Open the stop valve.
NO
NO
NO
YES
YES
NO
NO
NO
YES
YES
YES
YES
NO
NO
Power OFF
Power OFF
and the Power
ON again
Check if
the stop valve is
open.
Check if
the compressor lead
wires are normal.
Check if the
wiring and connection to
the compressor
are normal.
Insulation
resistance of the compressor
is 100 k or
below.
Check 4
Check if the power transistor
is normal.
Failure
occurs again after restarting
the unit.
Failure
occurs again after restarting
the unit.
Compressor
coils are disconnected.
YES
YES
Replace inverter PCB (A3P).
Continue operation.
Replace inverter
compressor.
(
(
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check 4
: Referring to the information on page 306.