Basic Control Si34-704
86 Function
2. Basic Control
2.1 Normal Operation
2.1.1 List of Functions in Normal Operation
*1. PI control : Evaporator outlet superheated degree (SH) constant.
*2. PI control : Condenser outlet subcooled degree (SC) constant.
*1 and 2 : Refer “6.6 Electronic expansion valve control” on page 121.
2.2 Compressor PI Control
Compressor PI Control
Carries out the compressor capacity PI control to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
Part Name Symbol
(Electric
Symbol)
Function of Functional Part
Normal Cooling
Compressor (M1C, M2C)
PI control, High pressure protection, Low pressure protection,
Td protection, INV protection,
Outdoor unit fan (M1F) Cooling fan control
Four way valve 20S1 (Y1R) OFF
Main motorized valve EV1 (Y1E) 480 pls
Subcool heat exchanger
electronic expansion valve
EV2 (Y2E) PI control
Hot gas bypass valve SVP (Y1S) OFF
Accumulator oil return valve SV0 (Y2S) ON
Indoor unit actuator Normal cooling
Fan
Thermostat ON unit Remote controller setting
Stopping unit OFF
Thermostat OFF unit Remote controller setting
Electronic
expansion
valve
Thermostat ON unit Normal opening
*
1
Stopping unit 0 pls
Thermostat OFF unit 0 pls
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te : Low pressure equivalent saturation
temperature (°C)
Te set value (Make this setting while in Setting
mode 2.)
TeS : Target Te value
(Varies depending on Te setting, operating
frequency, etc.)
*On multi-outdoor-unit systems, this control is made
according to values of the first-priority unit, which is
detected with the pressure sensor.
Te setting
LM (Normal)
(factory
setting)
H
369