Si34-704 Symptom-based Troubleshooting
Troubleshooting 181
15 The outdoor unit
compressor or
the outdoor unit
fan does not
stop.
After stopping operation It stops in order to prevent oil or
refrigerant from dwelling.
Normal operation.
It stops after a lapse of
approximately 5 to 10 minutes.
16 The outdoor gets
hot.
While stopping operation The reason is that the compressor
is warmed up to provide smooth
startup of the system.
Normal operation.
17 The system does
not cool air well.
The system is in dry operation. The reason is that the dry
operation serves not to reduce
the room temperature where
possible.
Change the system to cooling
operation.
Symptom Supposed Cause Countermeasure