Daikin RXYSQ5PA7V1B [175/282] Outdoor unit actuation of high pressure switch

Daikin RXYSQ5PA7V1B [175/282] Outdoor unit actuation of high pressure switch
Troubleshooting by Indication on the Remote Controller SiBE34-802
164 Troubleshooting
3.19
E3
Outdoor Unit: Actuation of High Pressure Switch
Remote
Controller
Display
E3
Applicable
Models
RXYSQ4~6PA
Method of
Malfunction
Detection
Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Decision
Conditions
Error is generated when the HPS activation count reaches the number specific to the operation
mode.
(Reference) Operating pressure of high pressure switch
Operating pressure: 4.0MPa
Reset pressure: 3.0MPa
Supposed
Causes
Actuation of outdoor unit high pressure switch
Defect of High pressure switch
Defect of outdoor unit PC board (A1P)
Instantaneous power failure
Faulty high pressure sensor