Field Settings SiBE27-702
122 Test Operation
Graph 2 Target evaporating temperature control when "low humidity application" is selected. Field
setting 16(26)-2-03:
Note:
Remote controller setting temp.
Te target limitted 20˚C
(to protect the comp.)
Te (see note) target acceptable area
Indoor temp. > setting Te target down
Indoor temp. < setting Te target up
Te target limitted 0˚C
Freeze protection
(40min. integrated coil temp. -1˚C)
Te target acceptable area
Te target
(˚C)
Indoor Temp
(˚C DB)
Te by LP sensor RZQ71B9V3B, RZQ71·100B7V3B, RZQ100~140C7V1B,
RZQS125·140C7V1B
Te by calculation RZQ100~140B8W1B