Daikin RZQ100B8W1B [229/344] Troubleshooting

Daikin RZQ100B8W1B [229/344] Troubleshooting
Troubleshooting by Remote Controller Display / LED Display SiBE27-702
216 Troubleshooting
Troubleshooting
Turn the main power supply
off, and then disconnect the
connection between the
compressor and inverter.
Is the
secondary
current of the inverter
higher than A (see
below) for each
phase?
Is the
inverter
output voltage
generated
approximately at the same
increasing speed on each
phase after turning
on again? ()
(U-V, V-W,
W-U)
Continuity check in the
power transistor (IGBT)
Is the continuity
normal?
YES
NO
NO
YES
NO
* When operating compressor
with compressor output line
disconnected, the compressor
stops due to malfunction after
elapsed time of 5 seconds.
Therefore, check the voltage
increase for 5 seconds.
Cooling
Heating
Cooling
Heating
Cooling
Heating
Detection value
17A × 5 seconds or 14.8A × 260 seconds
31A × 5 seconds or 21.1A × 260 seconds
17A × 5 seconds or 12.1A × 260 seconds
17A × 5 seconds or 14.1A × 260 seconds
Compressor overload
Inspection of the compressor
and refrigerant system is
required.
Compressor inspection
Inspect according to the
diagnosis procedure for
abnormal noises, vibration,
operating status, etc.
of the compressor.
Electronic thermal detection value
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
RZQ71B9V3B,RZQS71·100B7V3B
RZQ100~140,RZQS125·140C7V1B
RZQ100~140 B8W1B
RZQ71B9, RZQS71·100B7
(1φ), RZQ100~140B8 (3φ):
Replace the outdoor
inverter PC board (A2P).
RZQ100~140C7,
RZQS125·140C7 (1φ):
Replace the inverter PC
board (A2P).
RZQ71B9, RZQS71·100B7
(1φ), RZQ100~140B8 (3φ):
Replace the outdoor
inverter PC board (A2P).
RZQ100~140C7,
RZQS125·140C7 (1φ):
Replace the inverter PC
board (A2P).
Check 11
(P248)