Daikin RYN60E3V1B [273/300] Removal of sound blanket

Daikin RYN60E3V1B [273/300] Removal of sound blanket
Outdoor Unit SiBE04-705
262 Removal Procedure
2.2.6 Removal of Sound Blanket
Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step Procedure Points
1
Undo the 2 Velcro
tapes off the sound
blanket, and open the
sound blanket (outer
sleeve).
2
Remove the sound
blanket (top upper).
The sound blanket is fragile.
Carefully pass the discharge
pipe through it.
3
Remove the screw from
the partition plate and
open the plate slightly
to the left for easy work.
Velcro tapes
(R7013)
(R7014)
(R7015)