Daikin CDX25AVMA [175/268] Indoor outdoor unit installation drawings

Daikin CDK60AVMA [175/268] Indoor outdoor unit installation drawings
Outdoor Units ED12-321A
170 Installation Manual
Indoor/outdoor Unit Installation Drawings
Cut thermal insulation
pipe to an appropriate
length and wrap it with
tape, making sure that no
gap is left in the insulation
pipe’s cut line.
Wrap the insulation
pipe with the finishing
tape from bottom to top.
Caulk
pipe hole
gap
with putty.
(Foot bolt-hole centres)
58cm
Foot bolt-hole
centres
33cm
25 cm from wall
Allow space for piping
and electrical servicing.
Allow 30 cm of work
space below the
ceiling surface.
If there is the danger of the unit falling
or overturning, fix the unit with
foundation bolts, or with wire or other
means.
If the location does not have good
drainage, place the unit on a level
mounting base (or a plastic pedestal).
Install the outdoor unit in a level
position. Failure to do so may result in
water leakage or accumulation.
Level mounting base
(available separately)
Clamping material
Insulation tube
Service lid
Tape
Also insulate the connection on the outdoor unit.
Use tape or insulating material on all connections
to prevent air from getting in between the copper
piping and the insulation tube.
Be sure to do this if the outdoor unit is installed
above.
▲■
20
For installation of the indoor units, refer to the installation manual which was provided with the units.
(The diagram shows a wall-mounted indoor unit.)
Do not connect the embedded branch piping and the outdoor unit when only carrying out piping work without
connecting the indoor unit in order to add another indoor unit later.
Make sure no dirt or moisture gets into either side of the embedded branch piping.
See “6 Refrigerant Piping Work” in “Outdoor Unit” for details.
It is impossible to connect the indoor unit for one room only. Be sure to connect at least 2 rooms.
CAUTION
Precautions on Installation
Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
In accordance with the foundation drawing in fix the unit securely by means of the foundation bolts. (Prepare four sets of
M8 or M10 foundation bolts, nuts and washers each which are available on the market.)
It is best to screw in the foundation bolts until their length are 20 mm from the foundation surface.
When installing the unit on the frame, fix water proof plate within 150 mm from the bottom of the unit to prevent water