ED12-321A Electric Characteristics
SUPER MULTI NX B-Series Cooling Only 67
2
11.2 4MKD90BVMA
Cooling (50 / 60Hz 220V)
3D039725#3
3D039725#4
Combination
Units Power Supply Comp. OFM IFM
Hz Volts Min. Max. MCA MFA RLA W FLA W FLA
2.5
50/60 220 198 242
5.5
20
3.2
60 0.55
40 0.23
3.5 8.5 5.6 40 0.23
5.0 10.2 7.1 40 0.23
6.0 12.0 9.8 45 0.25
7.1 14.5 12.1 50 0.28
2.5+2.5 10.4 6.6 80 0.45
2.5+3.5 12.4 9.2 80 0.45
2.5+5.0 12.5 11.7 80 0.45
2.5+6.0 14.4 11.9 85 0.48
2.5+7.1 16.0 12.2 90 0.50
3.5+3.5 14.1 11.6 80 0.45
3.5+5.0 15.2 12.1 80 0.45
3.5+6.0 15.2 12.1 85 0.48
3.5+7.1 16.5 12.9 90 0.50
5.0+5.0 14.9 11.7 80 0.45
5.0+6.0 14.9 12.2 85 0.48
5.0+7.1 15.7 12.6 90 0.50
6.0+6.0 15.2 12.0 90 0.50
6.0+7.1 15.7 12.6 95 0.53
7.1+7.1 15.7 12.4 100 0.55
2.5+2.5+2.5 12.4 11.0 120 0.68
2.5+2.5+3.5 14.0 11.8 120 0.68
2.5+2.5+5.0 13.5 11.3 120 0.68
2.5+2.5+6.0 14.6 11.6 125 0.70
2.5+2.5+7.1 15.3 12.4 130 0.73
2.5+3.5+3.5 14.4 12.2 120 0.68
2.5+3.5+5.0 14.6 11.9 120 0.68
2.5+3.5+6.0 14.6 12.4 125 0.70
2.5+3.5+7.1 15.7 13.4 130 0.73
2.5+5.0+5.0 14.6 12.8 120 0.68
2.5+5.0+6.0 14.8 13.0 125 0.70
2.5+5.0+7.1 14.0 12.6 130 0.73
2.5+6.0+6.0 14.0 12.3 130 0.73
3.5+3.5+3.5 14.9 12.3 120 0.68
3.5+3.5+5.0 14.9 12.7 120 0.68
3.5+3.5+6.0 14.9 13.0 125 0.70
3.5+3.5+7.1 16.0 13.1 130 0.73
3.5+5.0+5.0 15.0 13.3 120 0.68
3.5+5.0+6.0 14.0 12.6 125 0.70
3.5+6.0+6.0 15.3 12.6 130 0.73
5.0+5.0+5.0 13.8 12.5 120 0.68
2.5+2.5+2.5+2.5 13.0 9.2 160 0.90
2.5+2.5+2.5+3.5 13.7 10.1 160 0.90
2.5+2.5+2.5+5.0 14.3 11.4 160 0.90
2.5+2.5+2.5+6.0 14.6 11.6 165 0.93
2.5+2.5+2.5+7.1 15.1 11.4 170 0.95
2.5+2.5+3.5+3.5 15.0 10.7 160 0.90
2.5+2.5+3.5+5.0 14.7 11.9 160 0.90
2.5+2.5+3.5+6.0 15.2 12.1 165 0.93
2.5+2.5+5.0+5.0 15.6 11.6 160 0.90
2.5+3.5+3.5+3.5 15.3 12.0 160 0.90
2.5+3.5+3.5+5.0 15.8 12.6 160 0.90
2.5+3.5+3.5+6.0 15.8 11.6 165 0.93
3.5+3.5+3.5+3.5 15.2 13.0 160 0.90
3.5+3.5+3.5+5.0 15.8 11.6 160 0.90
SYMBOLS: NOTES:
MCA : MIN. CIRCUIT AMPS (A) 1. RLA is based on the following conditions.
Power Supply: 50 / 60Hz 220V
Cooling
Indoor temp.: 27°CDB/19°CWB
Outdoor temp.: 35°CDB.
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the value of MCA.
4. Instead of fuse, use circuit breaker.
MFA : MAX. FUSE AMPS (A)
RLA : RATED LOAD AMPS (A)
OFM : OUTDOOR FAN MOTOR
IFM : INDOOR FAN MOTOR
FLA : FULL LOAD AMPS (A)
W : FAN MOTOR RATED OUTPUT (W)