EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
# Code Description
[7.7.2.1] [0‑00]
[0‑01]
[0‑02]
[0‑03]
<< continuation
[0‑03]: Low outdoor ambient temperature.
40°C~+5°C (default: –10°C)
[0‑02]: High outdoor ambient temperature.
10°C~25°C (default: 15°C)
[0‑01]: Desired leaving water temperature
when the outdoor temperature equals or
drops below the low ambient temperature.
[9‑05]°C~[9‑06]°C (default: 60°C).
Note: This value should be higher than [0-00]
as for low outdoor temperatures warmer
water is required.
[0‑00]: Desired leaving water temperature
when the outdoor temperature equals or
rises above the high ambient temperature.
[9‑05]°C~min(45, [9‑06])°C (default: 35°C).
Note: This value should be lower than [0-01]
as for high outdoor temperatures less warm
water is required.
# Code Description
[7.7.2.2] [0‑04]
[0‑05]
[0‑06]
[0‑07]
Only for EHYHBX08. Set weather-
dependent cooling:
[0-04]
[0-05]
T
a
T
t
[0-07] [0-06]
T
t
: Target leaving water temperature
(additional)
T
a
: Outdoor temperature
continued >>