Daikin EHYHBH05AFV32 [43/252] Installation site requirements of the indoor unit

Daikin EVLQ08CAV3 [43/252] Installation site requirements of the indoor unit
6 | Preparation
Installer reference guide
43
EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
6.2.3 Installation site requirements of the indoor unit
INFORMATION
Also read the precautions and requirements in the "1 General safety
precautions"[46].
Mind the measurement guidelines:
Maximum refrigerant piping length between indoor unit and
outdoor unit
20m
Minimum refrigerant piping length between indoor unit and
outdoor unit
3m
Maximum height difference between indoor unit and outdoor
unit
20m
Maximum equivalent piping length between the 3‑way valve
and the indoor unit (for installations with domestic hot water
tank)
3m
(a)
Maximum equivalent piping length between the domestic hot
water tank and the indoor unit (for installations with domestic
hot water tank)
10m
(a)
(a) Piping diameter 0.75".
Mind the following spacing installation guidelines:
>500
300
300
10 350 500
(mm)
Do NOT install the unit in places such as:
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
Sound sensitive areas (e.g. near a bedroom), so that the operation noise will
cause no trouble.
In places with high humidity (max. RH=85%), for example a bathroom.
In places where frost is possible. Ambient temperature around the indoor unit
must be >5°C.
The indoor unit is designed for indoor installation only and for ambient
temperatures ranging 5~35°C in cooling mode and 5~30°C in heating mode.