Daikin EHYHBH05AFV32 [163/252] Configuration

Daikin EHYHBX08AFV3 [163/252] Configuration
8 | Configuration
Installer reference guide
163
EVLQ05+08CAV3 + EHYHBH05AF + EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
# Code Description
[A.6.3.3] [5-05] Value: Only applicable in case of full time
power limitation mode.
0A~50A, step: 1A (default: 50A)
[A.6.3.4] [5-09] Value: Only applicable in case of full time
power limitation mode.
0kW~20kW, step: 0.5kW (default: 20kW)
Amp. limits for DI: Only applicable in case of power limitation mode based
on digital inputs and based on current values.
[A.6.3.5.1] [5-05] Limit DI1
0A~50A, step: 1A (default: 50A)
[A.6.3.5.2] [5-06] Limit DI2
0A~50A, step: 1A (default: 50A)
[A.6.3.5.3] [5-07] Limit DI3
0A~50A, step: 1A (default: 50A)
[A.6.3.5.4] [5-08] Limit DI4
0A~50A, step: 1A (default: 50A)
kW limits for DI: Only applicable in case of power limitation mode based on
digital inputs and based on power values.
[A.6.3.6.1] [5-09] Limit DI1
0kW~20kW, step: 0.5kW (default: 20kW)
[A.6.3.6.2] [5-0A] Limit DI2
0kW~20kW, step: 0.5kW (default: 20kW)
[A.6.3.6.3] [5-0B] Limit DI3
0kW~20kW, step: 0.5kW (default: 20kW)
[A.6.3.6.4] [5-0C] Limit DI4
0kW~20kW, step: 0.5kW (default: 20kW)
Average timer
The average timer corrects the influence of ambient temperature variations. The
weather-dependent set point calculation is done on the average outdoor
temperature.
The outdoor temperature is averaged over the selected time period.
# Code Description
[A.6.4] [1-0A] Outdoor average timer:
0: No averaging
1: 12hours (default)
2: 24hours
3: 48hours
4: 72hours

Содержание

Похожие устройства

Скачать