ULTIMA COMPACT FREECOOL Chillers
Chillers
20
Installation & Maintenance : 903-132 IM E 06/05/A
Installation Data
ELECTRICAL DATA
UCFC75D-2/1 UCFC100D-2/1 UCFC125D-3/1 UCFC150D-3/1 UCFC160D-6/2
Unit Data
Nominal Run Amps (1) A 50 62 79 93 99
Maximum Start Amps (2) A 140 167 217 246 252
Permanent Supply VAC 230 V 1 PH 50 Hz
Mains Supply VAC 400 V 3 PH 50 Hz
Rec Permanent Fuse Size A 16 16 16 16 16
Rec Mains Fuse Size A 63 80 125 125 125
Max Permanent Incoming Cable
Size
mm²
4 mm² terminals
Max Mains Incoming Cable Size mm² 70 (direct to MCCB) Direct to Bus Bar
Control Circuit VAC 24V/230VAC
Evaporator
Pad Heater Rating W 40 40 80 80 100
External Trace Heating
Available (fitted by others) W 500 500 500 500 500
Condenser Fan - Per Fan
Full Load Amps A 1.75 1.75 1.75 1.75 1.75
Locked Rotor Amps A 6.20 6.20 6.20 6.20 6.20
Motor Rating kW 0.98 0.98 0.98 0.98 0.98
Compressor - Per Compressor
Quantity 4 4 2 + 2 4 4
Motor Rating kW 6.2 8.1 8.1 / 11.7 11.7 11.7
Nominal Run Amps (1) A 11.7 14.6 14.6 / 22.0 22.0 22.0
Sump Heater Rating W 65.0 65.0 65.0 / 75.0 75.0 75.0
Start Amps (2) 98.0 120.0 175.0 / 120.0 175.0 175.0
Type Of Start Direct on line
QUIET DQ UCFC75DQ-2/1 UCFC100DQ-3/1 UCFC125DQ-3/1 UCFC150DQ-4/1 UCFC160DQ-6/2
All data as above except:
Condenser Fan - Per Fan
Full Load Amps A 1.15 1.15 1.15 1.15 1.15
Locked Rotor Amps A 2.10 2.10 2.10 2.10 2.10
Motor Rating kW 0.68 0.68 0.68 0.68 0.70
SUPER QUIET DSQ UCFC75DSQ-2/1 UCFC100DSQ-3/1 UCFC125DSQ-4/1 UCFC150DSQ-4/1 UCFC160DSQ-8/2
All data as above except:
Condenser Fan - Per Fan
Full Load Amps A 0.83 0.83 0.83 0.83 0.83
Locked Rotor Amps A 1.50 1.50 1.50 1.50 1.50
Motor Rating kW 0.32 0.32 0.32 0.32 0.32
OPTIONAL EXTRAS
Power Factor Correction
Nominal Run Amps (1) A 48 55 71 85 91
Maximum Start Amps (2) A 140 167 217 246 252
Recommended Mains Fuse A 63 80 125 125 125
Compressor Nominal Run
Amps - Per Compressor
A
4 x 11 4 x 13 2 x 20 / 2 x 13 4 x 20 4 x 20
Electronic Soft-Start
Nominal Run Amps (1) A 50 62 79 93 99
Maximum Start Amps (2) A 97 119 147 176 182
Recommended Mains Fuse A 63 80 125 125 125
Single Head Pump (or Run/Standby)
Unit Nominal Run Amps (1) A 55 67 86 98 105
Recommended Mains Fuse A 80 100 125 160 160
Motor Rating kW 2.2 2.2 3.0 3.0 7.5
Full Load Amps
A 4.8 4.8 6.8 6.8 14.7
Larger Single Head Pump
(Or Run/Standby)
Unit Nominal Run Amps (1) A 57 69 85 108 112
Recommended Mains Fuse A 80 100 125 160 160
Motor Rating kW 3.0 3.0 7.5 7.5 11
Full Load Amps
A 6.8 6.8 15.5 15.5 21.4
Twin Head Pump
Unit Nominal Run Amps (1) A 56 68 85 99 105
Recommended Mains Fuse A 80 100 125 160 160
Motor Rating kW 3.0 3.0 3.0 3.0 7.5
Full Load Amps
A 6.1 6.1 6.1 6.1 14.7
Larger Twin Head Pump
Unit Nominal Run Amps (1) A 56 70 87 102 112
Recommended Mains Fuse A 80 100 125 160 160
Motor Rating kW 3.0 4.0 4.0 4.0 11
Full Load Amps
A 6.1 7.7 7.7 7.7 21.4
(1) Based at 12/7°C water and 30°C ambient
(2) Starting amps refers to the direct on line connections.