Daikin EWYQ005AAV3P [102/170] 32 part 3 troubleshooting

Daikin EWAQ007AAV3P [102/170] 32 part 3 troubleshooting
Error Codes: Outdoor Units ESIE06-04
3–32 Part 3 – Troubleshooting
3
1
3
4
5
Troubleshooting
P4: Radiation fin thermistor
J3: Discharge pipe thermistor
J6: Outdoor heat exchanger thermistor
H9: Outdoor air thermistor
See also: "Check No.06" on page 3-53
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Reconnect.
Reconnect.
Replace the following
thermistor.
Hydro-box heat
exchanger thermistor
Replace the outdoor unit PCB.
(Replace the hydro-box PCB.)
Replace defective one(s) of the
following thermistors.
Radiation fin thermistor
Discharge pipe
temperature thermistor
Outdoor unit heat
exchanger temperature
thermistor
Outdoor air thermistor
NO
YES
YES
YES
NO
NO
Error displayed
again on remote controller?
Connector or
thermistor disconnected?
NO
YES
Normal?
hydro-box
heat exchanger thermistor
functioning?
Turn on the power again.
Check No. 06
Check the thermistor resistance
value.
Check No. 06
Check the hydro-box heat
exchanger thermistor resistance
value in the heating mode.