ESIE06-04 Error Codes: Outdoor Units
Part 3 – Troubleshooting 3–33
3
3
4
5
1
3.14 “L3 Switch Box Temperature Rise
Error code L3
Method of
malfunction
detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Malfunction
decision conditions
With the compressor off, the radiation fin temperature is above 95°C. (Reset is made when the
temperature drops below 80°C.)
Supposed causes
P Fin temperature rise due to defective outdoor unit fan
P Fin temperature rise due to short-circuit
P Fin thermistor defective
P Connector in poor contact
P Outdoor unit PCB defective