5.11 Capacitor Voltage Check
Check No.12 Before this checking, be sure to check the main circuit for short-circuit.
P Checking the capacitor voltage
P With the circuit breaker still on, measure the voltage according to the drawing of the model in
question. Be careful never to touch any live parts
OL lead wire
Thermistor lead wire
Fan motor lead wire
Electronic expansion valve
lead wire
Reversing solenoid
valve lead wire
(Heat pump type only)
Compressor lead wire
Reactor lead wire
Multimeter
(DC voltage range)