ESIE06-04 Error Codes: Outdoor Units
Part 3 – Troubleshooting 3–35
3
3
4
5
1
3.15 “L4 Radiation Fin Temperature Rise
Error code L4
Method of
malfunction
detection
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the compressor
on.
Malfunction
decision conditions
P If the radiation fin temperature with the compressor on is above 105°C,
P The error is cleared when the temperature drops below 99°C.
P If a radiation fin temperature rise takes place 4 times successively, the system will be shut down.
P The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
Supposed causes
P Fin temperature rise due to defective outdoor unit fan
P Fin temperature rise due to short-circuit
P Fin thermistor defective
P Connector in poor contact