ESIE06-04 Additional Checks for Troubleshooting
Part 3 – Troubleshooting 3–59
3
3
4
5
1
5.10 Inverter Units Refrigerant System Check
Check No.11
Correct the problem.
Conduct vacuum drying.
Replace the refrigerant.
Conduct the check after operating the
equipment for a sufficient length of time.
YES
YES
YES
NO
NO
Refrigerant system check
Check for gas leaks.
See the section on insufficient gas
detection.
Is
the discharge
thermistor disconnected from
the holder?
Is any moisture
found in sight glass?