ESIE06-04 Error Codes: Outdoor Units
Part 3 – Troubleshooting 3–13
3
3
4
5
1
3.3 “E5” OL Activation (Compressor Overload)
Error code E5
Method of
malfunction
detection
A compressor overload is detected through compressor OL.
Malfunction
decision conditions
P If the compressor OL is activated twice, the system will be shut down.
P The error counter will reset itself if this or any other error does not occur during the following
60-minute compressor running time (total time).
* The operating temperature condition is not specified.
Supposed causes
P Refrigerant shortage
P Four way valve malfunctioning
P Outdoor unit PCB defective
P Water mixed in the local piping
P Electronic expansion valve defective
P Stop valve defective