Daikin EWWQC13AJYNN/A [11/72] Table 5 ewwq 440 c22 ajynn a technical data

Daikin EWWQ550AJYNN/A [11/72] Table 5 ewwq 440 c22 ajynn a technical data
D -808 C – 08/01 A – EN Pag. 11/72
Table 5 - EWWQ 440-C22 AJYNN/A - Technical Data
TECHNICAL SPECIFICATIONS EWWQ – AJYNN/A 440 550 650 750 800
Capacity Cooling kW 431 527 653 740 818
Type Stepless
Capacity control
Minimum capacity % 25 25 25 25 25
Unit power input Cooling kW 87 105 128 146 162
EER 4.97 5.03 5.09 5.07 5.05
ESEER 5.58 5.61 5.69 5.67 5.64
Colour RAL7032
Casing
Material Galvanized and painted steel sheet
Height mm 2000 2000 2000 2001 2000
Width mm 1261 1261 1261 1260 1316
Dimensions Unit
Depth mm 3987 3987 3987 3855 3854
Unit kg 2322 2403 2464 2738 2407
Weight
Operating Weight kg 2594 2685 2745 3158 2815
Type Shell and tubes
Water volume l 220 213 200 334 325
Nominal water flow
rate
Cooling l/s 20.6 25.2 31.2 35.4 39.1
Nominal Water
pressure drop
Cooling kPa 59 73 76 68 60
Water heat exchanger
Evaporator
Insulation material Closet cell foam elastomer
Type Shell and tubes
Number of condensers No. 1 1 1 1 1
Water volume l 52 69 81 86 83
Nominal water flow
rate
Cooling l/s 24.7 30.2 37.3 42.3 46.8
Nominal Water
pressure drop
Nominal Water
pressure drop
kPa 52 42 43 48 62
Water heat exchanger
Condenser
Insulation Material Expanded elastomer
Type Semi-hermet. single screw compr.
Oil charge l 16 16 16 16 16
Compressor
Quantity 1 1 1 1 1
Sound Power Cooling dBA 100.9 101.7 102.6 102.7 102.0
Sound level
Sound Pressure Cooling dBA 82 83 84 84 83
Refrigerant type
R410A
R410
A
R410A R410A R410A
Refrigerant charge kg 95 95 95 95 110
Refrigerant circuit
N. of circuits 1 1 1 1 1
Piping connections Evaporator water inlet/outlet mm 219.1 219.1 219.1 219.1 219.1
Piping connections Condenser water inlet/outlet in 5” 5” 5” 5” 5”
Safety devices High pressure (pressure switch)
Safety devices Low pressure (pressure switch)
Safety devices Emergency stop
Safety devices High discharge temperature on the compressor
Safety devices Phase monitor
Safety devices Low pressure ratio
Safety devices High oil pressure drop
Safety devices Low oil pressure
Notes
Cooling capacity, unit power input in cooling and EER are based on the following conditions:
evaporator 12°C/7°C; condenser 30/ 35°C.

Содержание

Скачать