Daikin FXDQ25PVET [119/394] Under fin temperature protection control

Daikin FXDQ20PVET [119/394] Under fin temperature protection control
Protection Control Si34-704
108 Function
4.4 Inverter Protection Control
Inverter current protection control and inverter fin temperature control are performed to prevent
tripping due to a malfunction, or transient inverter overcurrent, and fin temperature increase.
In the case of multi-outdoor-unit system, each INV compressor performs these controls in
the following sequence.
[Inverter overcurrent protection control]
[Inverter fin temperature control]
Nomal operation
Under inverter current
protection control
Invertercurrent >14.7A
Inverter current standby
Inverter current <14.7A
INV upper limit frequency
= max
INV upper limit frequency: 1-step down
from current compressor frequency
INV upper limit frequency: 1-step up from
current compressor frequency
Inverter current >14.7A
Inverter current<14.7A continues
for 20 sec. or more.
Inverter current > 16.1A continues for 260 sec.
&
When occurring 4 times within 60 min.,
the malfunction code “L8 is output.
Tfin>84˚C
Fin temp. standby
Tfin<81˚C
INV upper limit rps = max
Under fin temperature
protection control
INV upper limit frequency: 1-step / 1 min up
from current compressor frequency Interval
Inverter fin temp.<81˚C continues
for 3 min. or more.
&
Tfin>84˚C
Tfin>93˚C
When occurring 4 times within 60 min.,
the malfunction code L4” is output.
Nomal operation
INV upper limit frequency: 1-step /
1 min down from current compressor
rps