Daikin FXDQ25PVET [236/394] Troubleshooting

Daikin FXDQ20PVET [236/394] Troubleshooting
Si34-704 Troubleshooting by Indication on the Remote Controller
Troubleshooting 225
Troubleshooting
Remove the foreign substances.
Correct the connection of the relay
connectors.
Insert the connector.
YES
Check if
any foreign substances
around the fan.
YES
YES
NO
NO
NO
Check in the monitor mode
12HP ~18HP class models have 2 fans.
Check electric motor (electric motor 1 or 2) corresponding
to malfunction code “E7” in the monitor mode of outdoor
unit PCB. (Refer to P. 194 ~ 195 for how to check)
Check the connection status of the connectors
Fan motor 1: relay connector or X1A, X2A of fan inverter
PCB. (A4P)
Fan motor 2: relay connector or X1A, X2A of fan inverter
PCB. (A8P)
Check the color of relay connectors
Fan motor 1: Both power supply wire and signal wire are
all white.
Fan motor 2: Both power supply wire and signal wire are
red in the PCB side and white in the motor side.
Cut the power supply OFF and wait for 10 minutes.
Check
if any connector is
disconnected.
Relay
connectors have
any connection
error.
Go on to the next page.
5HP
8HP
~
12HP
18HP
~
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
A3P A4P A8P