Daikin FXDQ25PVET [371/394] Note 1

Daikin FXDQ20PVET [371/394] Note 1
Example of connection (R-410A Type) Si34-704
360 Appendix
Note 1
When the equivalent pipe length between outdoor and indoor units is 90m or more, the size of main pipes (both gas-side and liquid-side) must be increased.
Depending on the length of the piping, the capacity may drop, but even in such case it is able to increase the size of main pipes.
1. Outdoor unit
2. Main pipes
3. Increase
4. The first refrigerant branch kit
5. Indoor unit
Note 2
Allowable length after the first refrigerant branch kit to indoor units is 40 m or less, however it can be extended up to 90 m if all the following conditions are satisfied. (In case of “ Branch with REFNET joint ” )
Note 3
If the pipe size above the REFNET header is φ34.9 or more, KHRP26M73HP is required.
Diameter of above case
Model
Gas Liquid
RX(Y)Q5 Type
φ19.1
φ12.7
RX(Y)Q8 Type
φ22.2
φ25.4*
φ12.7
RX(Y)Q10 Type
Not
Increased
Not
Increased
φ15.9
RX(Y)Q12 Type
Not
Increased
φ15.9
RX(Y)Q14 Type
RX(Y)Q16 Type
RX(Y)Q20 Type
RX(Y)Q22 Type
RX(Y)Q24 Type
RX(Y)Q26 Type
RX(Y)Q28 Type
RX(Y)Q34 Type
RX(Y)Q36 Type
RX(Y)Q38 Type
RX(Y)Q40 Type
RX(Y)Q48 Type
RX(Y)Q50 Type
RX(Y)Q52 Type
RX(Y)Q54 Type
φ31.8*
φ15.9
RX(Y)Q18 Type
φ31.8*
φ19.1
Model
Gas Liquid
φ31.8* φ19.1
φ31.8* φ19.1
Not
Increased
φ19.1
φ38.1* φ22.2
φ38.1* φ22.2
RX(Y)Q30 Type
φ38.1* φ22.2
RX(Y)Q32 Type
φ38.1* φ22.2
Model
Gas Liquid
φ38.1* φ22.2
Not
Increased
Not
Increased
Not
Increased
φ22.2
φ22.2
φ22.2
RX(Y)Q42 Type
RX(Y)Q44 Type
Not
Increased
Not
Increased
φ22.2
φ22.2
RX(Y)Q46 Type
Not
Increased
φ22.2
Model
Gas Liquid
Not
Increased
Not
Increased
Not
Increased
Not
Increased
φ22.2
φ22.2
φ22.2
φ22.2
*If available on the site, use this size.
Otherwise, it can not be increased.
*If available on the site, use this size. Otherwise it can not be increased.
Required Conditions Example Drawings
1.
It is necessary to increase the pipe size between the first branch kit
and the final branch kit. (Reducers must be procured on site)
However, the pipes that are same pipe size with main pipe must not
be increased.
2.
For calculation of Total extension length, the actual length of
above pipes must be doubled. (except main pipe and the pipes
that are not increased)
3. Indoor unit to the nearest branch kit 40 m
4. The difference between
[Outdoor unit to the farthest indoor unit] and [Outdoor unit
to the nearest indoor unit]
40 m
8 b+c+d+e+f+g+p 90 m
increase the pipe size of b, c, d, e, f, g
a+b×2+c×2+d×2+e×2+f×2+g×2
+h+i+j+k+l+m+n+p 1000 m
h, i, j....... p 40 m
The farthest indoor unit 8
The nearest indoor unit 1
(a+b+c+d+e+f+g+p)-(a+h) 40 m
Increase the pipe size as follows
φ 9.5 → φ12.7
φ12.7 → φ15.9
φ15.9 → φ19.1
φ19.1 → φ22.2
φ22.2 → φ25.4*
φ28.6 → φ31.8*
φ34.9 → φ38.1*
a
ABCDEFG
bcdef
g
hi j kl mn
1234567
8
H1
p
Outdoor unit
REFNET joint (A-G)
Indoor units ( 1 - 8 )
1
2
4
5
3