Daikin FXDQ25PVET [276/394] Troubleshooting

Daikin FXDQ32PVET [276/394] Troubleshooting
Si34-704 Troubleshooting by Indication on the Remote Controller
Troubleshooting 265
Troubleshooting
Check if the
temperature difference between
the suction pipe and the heat exchanger
is 20 degrees and over.
Check if the
property of suction pipe thermister
(A7T) and heat exchanger thermister
(R4T) are normal.
(*3)
Check if the
low pressure is 0.1MPa
or below. (1)
Check if the
property of low pressure
sensor is normal.
(2)
Replace the low pressure
sensor.
Replace the main PCB (A1P).
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NONO
YES YES
Remove the factor of
decreasing low pressure by
referring to Check 6 .
Remove the factor of
superheating by referring to
Check 3 .
Replace the thermister.
Replace the main PCB (A1P).
NONO
YES
Reset the operation using the remote controller then restart.
Set up a pressure gauge at the service port on the low
pressure side.
Reset the operation using the remote controller then restart.
3: Compare the thermister resistance value with the value on the surface
thermometer.
1: Check the low pressure value by using pressure gauge in operation.
2: Compare the actual measurement value by pressure sensor with the
value by the pressure gauge.
(To gain actual measurement value by pressure sensor, measure the
voltage at the connector [between (2)-(3)] and then convert the value
into pressure referring to P362.)
In heating mode
In cooling mode
Check 6
: Referring to the information on page 308.
Check 3
: Referring to the information on page 305.